Wide-Area Measurement Assisted Algorithm for Secure Backup Protection during Stressed Conditions

Author(s):  
Shivaji Raskar ◽  
Prashant Gawande ◽  
Sanjay Dambhare
2014 ◽  
Vol 29 (4) ◽  
pp. 1970-1977 ◽  
Author(s):  
Paresh Kumar Nayak ◽  
Ashok Kumar Pradhan ◽  
Prabodh Bajpai

2014 ◽  
Vol 513-517 ◽  
pp. 858-862
Author(s):  
Zhen Xing Li ◽  
Qiu Li ◽  
Tao Zhang

A novel algorithm is proposed for the purpose of improving the reliability and sensibility of fault component identification of wide area backup protection. The algorithm, called earth impedance comparison protection (EICP), is realized by comparing the ratios of different nodes, and the ratio is obtained by the bus voltage to the differential current. The advantages of EICP are verified in this paper using the measurement function of wide-area measurement system. The results of case studies show that EICP is superior to the current differential protection in terms of the sensitivity and to the directional pilot protection in terms of the dependability. The satisfactory results can be obtained when the EICP method is applied in the event of abnormal operations of protective relays and circuit breakers, measurement error scenarios or substation DC failure.


2015 ◽  
Vol 30 (3) ◽  
pp. 1410-1419 ◽  
Author(s):  
Javad Zare ◽  
Farrokh Aminifar ◽  
Majid Sanaye-Pasand

Sign in / Sign up

Export Citation Format

Share Document