scholarly journals Study on Impulse Breakdown Characteristics of Internal-Gap Lightning Protection Device Applied to 35 kV Distribution Line

Energies ◽  
2018 ◽  
Vol 11 (7) ◽  
pp. 1758 ◽  
Author(s):  
Zhen Fang ◽  
Bowen Wang ◽  
Jiazheng Lu ◽  
Zhenglong Jiang
Author(s):  
A. A. Kosyakov ◽  

The article points out the drawback of all the current instructions for the lightning protection device: the lack of instructions for calculating the lightning protection zones of an object located on a slope. The methods of applying the current instructions for the lightning protection device when placing an object on a slope are given, based on the assumption that lightning strikes the lightning rods vertically and perpendicular to the slope. The features of the choice of lightning protection characteristics (calculated points of the protected object, calculated heights of lightning rods, methods of constructing lightning protection zones) are described. A method for calculating the lightning protection zones of an object located on a slope is proposed, based on the assumption that lightning strikes lightning rods perpendicular to the slope, in particular, the concept of the axis of a conditional lightning rod shifted on the object plan for calculating lightning protection zones is introduced. The consequences of the application in engineering practice of the methodology for calculating the lightning protection zones of an object located on a slope, based on the assumption that lightning strikes the lightning rods perpendicular to the slope, are indicated. Using a pulse voltage generator, tests were performed on a model of a lightning rod located on a slope in order to determine the direction of lightning strikes-vertical or perpendicular to the slope. It was determined experimentally that the proposed method for calculating the lightning protection zones of an object located on a slope, based on the assumption that lightning strikes lightning rods perpendicular to the slope, should be used in cases where the protected objects are located on slopes with an angle of more than 25°.


2015 ◽  
Vol 1092-1093 ◽  
pp. 281-287
Author(s):  
Yao Zhang Yu ◽  
Jun Kang Ni ◽  
Jun Yu Han ◽  
Bin Ren ◽  
Ao An Li ◽  
...  

Since distribution lines have relatively weak insulation compared to power transmission lines, it is more liable to lightning damages. This paper reports a study of how overhead ground wire height and impulse ground resistance affect the lightning protection performance. The results obtained in this paper show that high overhead ground wire worsen the lightning protection performance while reducing the impulse ground resistance improves the lightning protection performance. Therefore, it is recommended to set the overhead ground wire lower and take necessary measures to reduce impulse ground resistance. The results obtained also confirm the crucial role of the overhead ground wire as a protection of distribution lines.


Author(s):  
Jinliang He ◽  
Shuiming Chen ◽  
Rong Zeng

Adopting covered conductors and compact configuration has become the tendency in the renovation of distribution network in China. Advantages of compact configuration are discussed in this paper, which can further save the passage of distribution line, and can easily realize multiple lines in a pole. The movement process of phase conductors is analyzed by the Chord Forced Equation of the mechanical theory to obtain the relationship between the phase spacing of triangle spacer and the span between two neighboring spacers. The suitable phase spacing and spacer span are presented for polymeric and composite spacers. The superiority of compact configuration against lightning protection comparing with traditional distribution lines was analyzed.


2021 ◽  
Vol 2137 (1) ◽  
pp. 012045
Author(s):  
Aihua Liu ◽  
Shuning Ma

Abstract Zinc oxide arrester is often used as lightning protection device in 10KV distribution network. In order to check the reliable operation of the zinc oxide arrester, preventive tests are often carried out. In this project, the intelligent tester adopts high-precision clamp current mutual inductance technology as the front-end acquisition mode of current signals; Magnetic isolation technology is used to ensure the accuracy of current and voltage sampling and the anti-interference ability and testing accuracy of the instrument are improved by using fast Fourier transform for data processing. The integrated application of several technologies provides a basis for judging the operating state of the 10kV zinc oxide arrester. The charged measurement of operating parameters of 10kV zinc oxide arrester is realized and the measurement efficiency is improved.


1994 ◽  
Vol 114 (6) ◽  
pp. 649-656
Author(s):  
Tokuji Masaki ◽  
Kouji Higuchi ◽  
Yoshihide Yokoi

Author(s):  
Xiao-gang Zhao ◽  
Yi Zhou ◽  
Yu-zhang Guo ◽  
Heng Li ◽  
Li-xin Zhao